POWER ENTRY MODULES WITH LINE FILTER
Actual information about approvals can be found on http://www.schurter.com/approvals
C14
70 C
Standard- or Medical-Filter
Description
- Panel mount: Screw-on version from front side - 4 Functions: Connector, Fuseholder with interchangeable fuse drawer for Fuselinks 5 x 20 mm or 6.3 x 20 mm 1- or 2-pole, Voltage selector (series-parallel), Line filter in standard and medical version - Quick connect terminals 4.8 x 0.8 mm - Alternative: version without line filter KE
Characteristics
- All single elements are already partial wired - For added safety "Extra-Safe" fuse drawers are available Fuse drawer meets requirements of medical standard IEC/EN 60601-1 The fuse drawer can only be opened with the aid of a tool The fuseholder is accessible from the equipment front - Qualified for use in equipment according IEC/EN 60950
Technical data
Ratings IEC Ratings UL/CSA Leakage current Dielectric strength 1 - 10 A @ Ta 40 C / 250 VAC; 50 Hz 1 - 10 A @ Ta 40 C / 125 VAC; 60 Hz standard < 0.5 mA (250 V / 60 Hz) medical < 5 A (250 V / 60 Hz) > 1.7 kVDC between L-N > 2.7 kVDC between L/N-PE Test voltage (2 sec) -25 C to 85 C 25/085/21, IEC 60068-1 from front side IP40 acc. to IEC 60529 Suitable for appliances with protection class I acc. to IEC 61140 Quick-connect terminals 4.8 x 0.8 mm Screw-on: max 8 mm Mounting screw torque max 0.5 Nm Thermoplastic, black, UL 94V-0 Appliance-inlet /-outlet C14 acc. to IEC/EN 60320-1, UL 498, CSA C22.2 no. 42 (for cold condition) pin-temperature 70 C, 10 A, Protection class I Fuseholder 1- or 2-pole, Shocksave category PC2 acc. to IEC/EN 60127-6, for fuse-links 5 x 20 or 6.3 x 32 mm Rated power acceptance @ Ta 5 x 20: 2.5 W (1-pole)/ 2 W (2-pole) per 23 C pole 6.3 x 32: 3.15 W (1-pole)/ 2.5 W (2pole) per pole Power acceptance @ Ta > Admissible power acceptance at higher 23C ambient temperature see derating curves. Take note of the information GENERAL PRODUCT INFORMATION Voltage selector series-parallel, 4, 3 or 2 switch positions or usable as 2-pole change-over switch Line filter Standard and medical version, IEC 60939, IEC 60601-1, UL 1283, UL 544, EN 133 200, CSA C22.2 no. 8 Technical details GENERAL PRODUCT INFORMATION
Allowable operation temp. Climatic category Degree of protection Protection class Terminals Panel thickness s Materials: Housing
1
[www.schurter.com]
CE
Dimensions
POWER ENTRY MODULES WITH LINE FILTER
Technical data of filter-components
Rated current Filter-Type [A] 1 2 4 6 10 1 2 4 6 10 Standard Version Standard Version Standard Version Standard Version Standard Version Medical Version (M5) Medical Version (M5) Medical Version (M5) Medical Version (M5) Medical Version (M5) Inductances Capacitance Capacitance L [mH] CX [nF] CY [nF] 2 x 10 2x4 2 x 1.5 2 x 0.8 2 x 0.3 2 x 10 2x4 2 x 1.5 2 x 0.8 2 x 0.3 68 68 68 68 68 68 68 68 68 68 2.2 2.2 2.2 2.2 2.2 1 1 1 1 1 R [MW]
Diagrams Standard version
Medical version
1) Line 2) Load x) External connection to be made by customer
1) Line 2) Load x) External connection to be made by customer
Derating curves Fuses 5 x 20 mm (1-pole)
Admissible power acceptance in Watt per pole Admissible power acceptance in Watt
Fuses 5 x 20 mm (2-pole, per pole)
Admissible power acceptance in Watt
Fuses 6,3 x 32 mm (1-pole)
Admissible power acceptance in Watt per pole
Fuses 6,3 x 32 mm (2-pole, per pole)
Ambient air temperature Ta C
Ambient air temperature Ta C
Ambient air temperature Ta C
Ambient air temperature Ta C
2
[www.schurter.com]
CE
Attenuation loss
Standard version
POWER ENTRY MODULES WITH LINE FILTER
- - - - differential mode _____ common mode
1A
2A
4A
6A
10 A
Medical version
1A
2A
4A
6A
10 A
Variants
Fuse drawer and voltage selector insert must be ordered separately. Order Number Rated current Filter-Type Fuseholder [A] CE16.5100.151 CE26.5100.151 CE36.5100.151 CE46.5100.151 CE66.5100.151 CE10.6100.151 CE20.6100.151 CE30.6100.151 CE40.6100.151 CE60.6100.151 CEA0.6100.151 CEC0.6100.151 CEE0.6100.151 CEG0.6100.151 CEL0.6100.151 1 2 4 6 10 1 2 4 6 10 2 4 6 1 10 10 Pcs Standard Version Standard Version Standard Version Standard Version Standard Version Standard Version Standard Version Standard Version Standard Version Standard Version Medical Version (M5) Medical Version (M5) Medical Version (M5) Medical Version (M5) Medical Version (M5) 1-pole 1-pole 1-pole 1-pole 1-pole 2-pole 2-pole 2-pole 2-pole 2-pole 2-pole 2-pole 2-pole 2-pole 2-pole
Packaging unit
Accessories
ACCESSORIES
3
[www.schurter.com]


▲Up To Search▲   

 
Price & Availability of CE106100151

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X